3 Points about Fire Pressure Reducing Valves
Today we share 3 points about fire pressure reducing valves as follows. 1. The use of pressure reducing valves to reduce pressure zoning water supply should comply with the following provisions. (1) The performance of the pressure reducing valve used for fire fighting water supply should be safe and reliable, and should meet the requirements of fire fighting water supply. (2) Fire pressure reducing valve should be selected according to the design flow and pressure of the fire water supply, and the design flow should be in the effective section of the pressure reducing valve flow pressure characteristic curve, and check at 150% of the design flow, the pressure reducing valve outlet dynamic pressure should not be less than 65% of the design value. (3) Each water supply partition should have no less than two groups of pressure reducing valves, and each group of pressure reducing valves should be set up as a backup pressure reducing valve; (4) Fire pressure reducing valves should only be